MR8880-20 Features
  • Engineered for use in extreme environments
    Thanks to its safe, CAT III 600V class design, the MR8880-20 can directly measure high voltages of up to 600V at demanding p/lants and other facilities. The recorder also features an extended operating temperature range of -10°C to 50°C and complies with JIS automotive vibration standards, demonstrating its ability to withstand the harsh measurement environments associated with automotive development.

  • Measure 3-phase power lines thanks to standard 4 channels of input
    The MR8880-20 can perform isolated measurement using its 4 channels of analog input, allowing it to measure 3-phase power lines.

  • Simple operation with the PRESETS configuration navigator function
    In the past, customer feedback has indicated that electrical measuring instruments are excessively difficult to configure and operate. The MR8880-20’s PRESETS configuration navigator function addresses these concerns by allowing users to simply select an application—for example, measuring a commercial power supply or monitoring a line for a voltage drop—and follow the on-screen instructions to configure the instrument.

  • Print measurement data on-site with the optional printer
    An optional A6-size printer can be used to print waveforms in the field, making it easier to hold effective evaluations at job sites. Data can also be stored in external storage media.
Measurement Applications
  • Plant equipment maintenance, inspections, and fault monitoring
  • Elevator maintenance, inspections, and fault monitoring
  • Train maintenance and inspections and rolling stock development
  • Automobile development, malfunction analysis, etc.
Basic Specifications
Measurement functionality • High-speed function (high-speed recording)
• Real-time function (real-time recording)
No. of input channels 4 channels of analog input + 8 channels of logic input (standard)
*Analog input channels are isolated from one another and other device circuitry. Logic input channels share a common ground with the device.
Max. sampling speed 1 MS/sec (1 μs period; all channels sampled simultaneously)
Internal memory capacity 14 bits × 1 Mword per channel (1 word = 2 bytes, not expandable)
External memory • CF card slot × 1 (up to 2 GB; supported formats: FAT/FAT32)
• USB memory × 1 (USB 2.0 Standard-A receptacle)
Communications interfaces USB 2.0 Mini-B receptacle × 1
Functionality: Device configuration and measurement using communications commands; transfer of files from CF/USB memory to a computer (USB drive mode)
Operating environment
(non-condensing)
• Operating temperature range: -10°C to 50°C
• Operating humidity range: 80% RH or less at -10°C to 40°C, 60% RH or less at 40°C to 45°C, 50% RH or less at 45°C to 50°C
• When powering the instrument with the Z1000 battery: 0°C to 40°C, 80% RH or less
• When charging the Z1000 battery: 10°C to 40°C, 80% RH or less
Storage environment (non-condensing) • Storage temperature range: -20°C to 60°C
• Storage humidity range: 80% RH or less at -20°C to 40°C, 60% RH or less at 40°C to 45°C, 50% RH or less at 45°C to 60°C
• Z1000 battery: -20°C to 40°C, 80% RH or less
Standard compliance • Safety: EN61010
• EMC: EN61326, EN61000-3-2, EN61000-3-3
• Vibration resistance: JIS D 1601, Type 1: passenger vehicles; conditions: equivalent to Type A
Charging function
(reference value at 23°C)
Charge time: Approx. 3 hours
(The charging function is activated by connecting the AC adapter while the BATTERY PACK Z1000 is attached to the instrument.)
External dimensions and weight
(including battery pack)
• Recorder only: Approx. 205 (W) × 199 (H) × 67 (D) mm, 1.76 kg
• With printer: Approx. 303 (W) × 199 (H) × 67 (D) mm, 2.26 kg
 
Analog Input Specifications
Measurement functionality 4-channel voltage measurement, switchable between instantaneous value (waveform) and RMS value
Input jacks Isolated BNC jacks (input resistance: 1 MΩ; input capacitance: 7 pF)
Max. rated input-to-ground voltage • 600 V AC/DC, measurement category III
• 300 V AC/DC, measurement category IV
(Inputs are isolated from other instrument circuitry. These figures represent the maximum voltage that can be applied between input channels and the instrument’s enclosure and between input channels themselves without damaging the instrument.)
Measurement ranges • 10 mV to 100 V/div, 13 ranges, full scale of 10 div
• AC voltage that can be measured/displayed using high-speed function: 600 Vrms
• Low-pass filter: 5/50/500/5k/50k Hz
Max. sampling speed 1 MS/s (4 channels sampled simultaneously)
Frequency characteristics DC to 100 kHz ±3 dB
Max. rated voltage between input terminals 600 V AC/DC
(Representing the maximum voltage that can be applied between input jacks without damaging the instrument.)